54
7 SETTINGS
7.1 Network Configuration Settings
7
SETTINGS
7.1
Network Configuration Settings
Set the parameters of the safety remote I/O module with the network parameters written to the CPU module of the master
station.
For the setting procedure for the master station, refer to the following.
User's manual for the master station used
Communication cycle interval setting
When using the safety remote I/O module, set values listed in the tables below for "Communication Period Interval Setting" of
"Basic Period Setting" of "Communication Period Setting" of "Basic Settings" of the network parameters.
■
For the safety remote I/O module with the firmware version of "02" or later
*1 To use the safety remote I/O module in this combination, set "Low-Speed" of "Multiple Period Setting" to "
16" for the master station, and
set "Communication Period Setting" to "Low-Speed" for the safety remote I/O module.
*2 To use the safety remote I/O module in this combination, do not set "Communication Period Setting" to "Low-Speed" for the safety
remote I/O module.
■
For the safety remote I/O module with the firmware version of "01"
*1 To use the safety remote I/O module in this combination, set "Low-Speed" of "Multiple Period Setting" to "
16" for the master station, and
set "Communication Period Setting" to "Low-Speed" for the safety remote I/O module.
*2 To use the safety remote I/O module in this combination, do not set "Communication Period Setting" to "Low-Speed" for the safety
remote I/O module.
Communication speed
Value that can be set
Master station
Safety remote I/O module
1Gbps
1Gbps
• When the value is set in increments of 1
s: 125.00
s or more and 10000.00
s or
less
• When the value is not set in increments of 1
s: 31.25
s, 62.50
s, 125.00
s,
250.00
s, 500.00
s, 1000.00
s, 2000.00
s, 4000.00
s, or 8000.00
s
100Mbps
• When the value is set in increments of 1
s: 125.00
s or more and 625.00
s or less
• When the value is not set in increments of 1
s: 125.00
s, 250.00
s, or 500.00
s
100Mbps
1Gbps
• When the value is set in increments of 1
s: 125.00
s or more and 10000.00
s or
less
• When the value is not set in increments of 1
s: 31.25
s, 62.50
s, 125.00
s,
250.00
s, 500.00
s, 1000.00
s, 2000.00
s, 4000.00
s, or 8000.00
s
100Mbps
• When the value is set in increments of 1
s: 500.00
s or more, 10000.00
s or less,
and divisible by 2
s
• When the value is not set in increments of 1
s: 500.00
s, 1000.00
s, 2000.00
s,
4000.00
s, or 8000.00
s
Communication speed
Value that can be set
Master station
Safety remote I/O module
1Gbps
1Gbps
• When the value is set in increments of 1
s: 125.00
s or more and 8000.00
s or
less
• When the value is not set in increments of 1
s: 31.25
s, 62.50
s, 125.00
s,
250.00
s, 500.00
s, 1000.00
s, 2000.00
s, 4000.00
s, or 8000.00
s
100Mbps
• When the value is set in increments of 1
s: 125.00
s or more and 500.00
s or less
• When the value is not set in increments of 1
s: 125.00
s, 250.00
s, or 500.00
s
100Mbps
1Gbps
• When the value is set in increments of 1
s: 125.00
s or more and 8000.00
s or
less
• When the value is not set in increments of 1
s: 31.25
s, 62.50
s, 125.00
s,
250.00
s, 500.00
s, 1000.00
s, 2000.00
s, 4000.00
s, or 8000.00
s
100Mbps
• When the value is set in increments of 1
s: 500.00
s or more, 8000.00
s or less,
and divisible by 2
s
• When the value is not set in increments of 1
s: 500.00
s, 1000.00
s, 2000.00
s,
4000.00
s, or 8000.00
s