Page 96
AiRanger SPL
PL-573
Technical Refer
e
nce
Parameter Settings
Number
Description
Instructions
P001
Operation
Enter "2" for
space
.
P002
Material
No entry required (preset for
liquid)
.
P003
Measurement Response
Enter "4" for
surge
(100 m/min, Failsafe
Timer = 0.1 minutes).
P004
Transducer
Enter "101" for
XCT-8
.
P005
Units
Enter "4" for
feet
.
P006
Empty
Enter "4.5" for
4.50 ft
(3 feet diameter plus
1.5 ft in standpipe).
P007
Span
Enter "3" for
3 ft
(vessel diameter).
P070
Failsafe Timer
No entry required, (preset by P003).
Parameter Settings for mA Output
Number
Description
Instructions
P200
mA Range
No entry required. (preset for
20 mA = low
level
, P001 = 2.)
P213
mA Max Limit
Enter "22" for
22.00 mA
.
P219
mA Failsafe
Enter "20.2" for
20.20 mA
.
Parameter Setting for Temperature Averaging
Number
Description
Instructions
P660
Temp Source
Enter "5" for average XCT-8 and TS-3
temperatures.
With process control equipment disabled, enter the RUN mode to monitor system
performance and alarm programming. (A Reading Measurement simulation (P920)
may be performed to verify mA output programming).
When satisfied with system performance and programming, connect the mA output to
the Programmable Logic Controller (PLC).
Note that on "power off" the mA output drops to 0.00 mA. During a power
interruption, the "last known" mA output value is maintained in memory for 1 hour
minimum. If power is interrupted beyond 1 hour, on power resumption, the mA output
immediately assumes the "new value".
Summary of Contents for AiRanger SPL PL-573
Page 1: ...AIRANGER SPL Instruction Manual PL 573 March 2001 IRANGER SPL 33455730 Rev 1 2 ...
Page 8: ...Page 8 AiRanger SPL PL 573 Specifications ...
Page 24: ...Page 24 AiRanger SPL PL 573 Installation ...
Page 86: ...Page 86 AiRanger SPL PL 573 Enhancement Param ...
Page 102: ...Page 102 AiRanger SPL PL 573 Maintenance ...
Page 108: ...Page 108 AiRanger SPL PL 573 Troubleshooting ...