Rate Parameters (P700 to P707)
P700
Max Fill Rate
Adjust the SPL response to increases in the actual material level (or advance to a
higher Failsafe Material Level, P071).
Enter a value slightly greater than the maximum vessel filling rate.
This value (in Units (P005) or % of Span (P007) per minute) is automatically altered
when Measurement Response (P003) is altered. See Technical Reference
Measurement Response.
Values:
0.000 to 9999
P701
Max Empty Rate
Adjust the SPL response to decreases in the actual material level (or advance to a
lower Failsafe Material Level, P071).
Enter a value slightly greater than the maximum vessel emptying rate.
This value (in Units (P005) or % of Span (P007) per minute) is automatically altered
when Measurement Response (P003) is altered. See Technical Reference
Measurement Response.
Values:
0.000 to 9999
P702
Filling Indicator
Enter the fill rate required to activate the LCD Material Filling indicator.
This value (in Units (P005) or % of Span (P007) per minute) is automatically set to
10% of the Max Fill Rate (P700).
Values:
-999 to 9999
P703
Emptying Indicator
Enter the empty rate required to activate the LCD Material Emptying indicator.
This value (in Units (P005) or % of Span (P007) per minute) is automatically set to
10% of the Max Empty Rate (P701) .
Values:
-999 to 9999
Summary of Contents for AiRanger SPL PL-573
Page 1: ...AIRANGER SPL Instruction Manual PL 573 March 2001 IRANGER SPL 33455730 Rev 1 2 ...
Page 8: ...Page 8 AiRanger SPL PL 573 Specifications ...
Page 24: ...Page 24 AiRanger SPL PL 573 Installation ...
Page 86: ...Page 86 AiRanger SPL PL 573 Enhancement Param ...
Page 102: ...Page 102 AiRanger SPL PL 573 Maintenance ...
Page 108: ...Page 108 AiRanger SPL PL 573 Troubleshooting ...