Page 48
AiRanger SPL
PL-573
Application Par
a
m
.
mA Output Parameters (P200 to P203, P210 to P215, P219)
If SPL mA outputs are to be used, alter the following parameters as required.
Note:
Otherwise, proceed to Operations.
When a mA Output Parameter is accessed, the mA symbol is displayed in the Point
Type field and the mA output number (corresponding to the SPL terminals) is
displayed in the Point Number field.
P200
mA Range
Enter the desired range of the mA output displayed.
Values:
0 = OFF
1 = 0 to 20 mA
2 = 4 to 20 mA (preset)
20 mA = high level (unless P001 = 2 or 3,
then 20 mA = low)
3 = 20 to 0 mA
4 = 20 to 4 mA
20 mA = low level (unless P001 = 2 or 3, then
20 mA = high)
P201
mA Function
Use this feature to alter the automatic mA output/measurement relationship, if
desired.
The mA Function automatically corresponds to "level", "space", or "distance" based
upon Operation (P001). If a Tank Shape (P050) is programmed, the mA Function
automatically corresponds to volume (unless the mA Allocation has been altered).
Values:
1 = level
2 = space
3 = distance
4 = volume
P203 (V)
mA Value / Transducer
View the current value of the mA output.
This is the Auxiliary Reading displayed when [mA] is pressed in the RUN mode.
Values:
0.000 to 22.00
Summary of Contents for AiRanger SPL PL-573
Page 1: ...AIRANGER SPL Instruction Manual PL 573 March 2001 IRANGER SPL 33455730 Rev 1 2 ...
Page 8: ...Page 8 AiRanger SPL PL 573 Specifications ...
Page 24: ...Page 24 AiRanger SPL PL 573 Installation ...
Page 86: ...Page 86 AiRanger SPL PL 573 Enhancement Param ...
Page 102: ...Page 102 AiRanger SPL PL 573 Maintenance ...
Page 108: ...Page 108 AiRanger SPL PL 573 Troubleshooting ...