PL-573
AiRanger SPL
Page 95
Technical Refer
e
nce
Example 2 - Space Measurement
This mode of operation is commonly used when remaining vessel capacity is of more
importance to the installation than the actual material level.
Space
For this example we'll assume the following:
•
the vessel is a 3 ft diameter by 15 ft long cylinder (including the parabolic ends of 1.5
ft each).
•
the maximum vessel filling rate is 1 ft per minute (slower at mid level).
•
a mA output scaled from 4 mA at Full to 20 mA at Empty is required for PLC
operation.
•
in the event of a measurement difficulty, failsafe operation is to be activated in 6
seconds.
•
if the difficulty doesn't subside, the mA output must immediately assume 22.00 mA.
•
an XCT-8 transducer is mounted in a standpipe so that the face is 18 in. above the
vessel top.
•
a TS-3 temperature sensor is mounted in the vessel to monitor liquid temperature.
1.5ft
(P052)
12.00 ft
(P053)
4.50 ft
(P006)
3.00 ft
(P007)
Summary of Contents for AiRanger SPL PL-573
Page 1: ...AIRANGER SPL Instruction Manual PL 573 March 2001 IRANGER SPL 33455730 Rev 1 2 ...
Page 8: ...Page 8 AiRanger SPL PL 573 Specifications ...
Page 24: ...Page 24 AiRanger SPL PL 573 Installation ...
Page 86: ...Page 86 AiRanger SPL PL 573 Enhancement Param ...
Page 102: ...Page 102 AiRanger SPL PL 573 Maintenance ...
Page 108: ...Page 108 AiRanger SPL PL 573 Troubleshooting ...