Page 70
AiRanger SPL
PL-573
Enhancement Pa
ra
m.
Values :
0 = off (preset)
1 = submergence transducer
P803
Shot/Pulse Mode
Use this feature to increase response independent from Measurement Response
(P003).
Select "short and long" to have short and long acoustic shots fired each time a vessel
is scanned. Select "short" to have only short shots fired if the Echo Confidence
(P805) produced by a short shot exceeds the short Confidence Threshold (P804).
This value is automatically altered when Measurement Response (P003) is altered.
See Technical Reference Measurement Response.
Values:
1 = short
2 = short and long
P804
Confidence Threshold
Use this feature when an incorrect material level is reported.
The short and long Confidence Thresholds are preset to 10 and 5 respectively. If the
Echo Confidence (P805) of a particular echo exceeds the Confidence Threshold, that
echo is considered for evaluation by Sonic Intelligence™.
Values:
x.y
x = short (0 to 99), y = long (0 to 99)
P805 (V)
Echo Confidence
Use this feature to monitor the effect of transducer aiming, location, and mechanical
transducer / mounting isolation.
This is the value displayed when
is pressed for 4 seconds in the RUN mode.
Both short and long shot Echo Confidence is displayed.
"--" is displayed if the respective shot (short or long) was not included in the evaluation.
"E" is displayed if the transducer cable is open or short circuited.
"--:-- is displayed if no shots have been taken yet.
Values:
x:y
x = short (0 to 99), y = long (0 to 99)
Summary of Contents for AiRanger SPL PL-573
Page 1: ...AIRANGER SPL Instruction Manual PL 573 March 2001 IRANGER SPL 33455730 Rev 1 2 ...
Page 8: ...Page 8 AiRanger SPL PL 573 Specifications ...
Page 24: ...Page 24 AiRanger SPL PL 573 Installation ...
Page 86: ...Page 86 AiRanger SPL PL 573 Enhancement Param ...
Page 102: ...Page 102 AiRanger SPL PL 573 Maintenance ...
Page 108: ...Page 108 AiRanger SPL PL 573 Troubleshooting ...