Application Par
a
m
.
Reading Parameters (P060 to P062)
If Reading alteration is required, alter the following parameters to:
•
alter the number of decimal places displayed.
•
convert to units other than Units (P005), % of Span (P007), or Max Volume (P051).
•
reference measurements to some point other than Empty (P006) or Span (P007).
Note:
If alteration is not required, proceed to Failsafe Parameters.
P060
Decimal Position
Enter the maximum number of decimal places to be displayed in the Reading.
In the RUN mode, the number of decimal places displayed is automatically adjusted
(if necessary) to prevent the number of Reading digits from exceeding display
capabilities.
This value is automatically altered when Units (P005) or Max Volume (P051) are
altered.
Values:
0 = no digits after the decimal point
1 = 1 digit after the decimal point
2 = 2 digits after the decimal point
3 = 3 digits after the decimal point
P061
Convert Reading
Enter the value to multiply the Reading by, (before display).
This feature is preset to 1.000 (no conversion).
e.g.
If the Reading is currently displayed in feet, to display in yards, enter 3.
Note:
Avoid entering a value that, when multiplied by the maximum current Reading,
could exceed 5 digits before the Decimal Position.
Values:
-999 to 9999
Summary of Contents for AiRanger SPL PL-573
Page 1: ...AIRANGER SPL Instruction Manual PL 573 March 2001 IRANGER SPL 33455730 Rev 1 2 ...
Page 8: ...Page 8 AiRanger SPL PL 573 Specifications ...
Page 24: ...Page 24 AiRanger SPL PL 573 Installation ...
Page 86: ...Page 86 AiRanger SPL PL 573 Enhancement Param ...
Page 102: ...Page 102 AiRanger SPL PL 573 Maintenance ...
Page 108: ...Page 108 AiRanger SPL PL 573 Troubleshooting ...