Page 30
AiRanger SPL
PL-573
Quick Start Para
m.
P004
Transducer
Enter the type of transducer connected to the SPL.
Values:
0 = not entered
100 = ST-H
106 = XPS-40
1 = ST-25
101 = XCT-8
107 = XLT-30
2 = ST-50
102 = XPS-10
108 = XLT-60
3 = ST-100
103 = XCT-12
109 = XLS-30
4 = LR-21
104 = XPS-15
110 = XLS-60
5 = LR-13
105 = XPS-30
111 = XKS-6
112 = XRS-5
P005 (G)
Units
Enter the units of measure desired for programming Empty (P006) and Span (P007).
Values:
1 = metres (m) (preset)
2 = centimetres (cm)
3 = millimetres (mm)
4 = feet (ft)
5 = inches (in)
P006
Empty
Enter the
maximum distance
(transducer face to vessel bottom) to be measured, in Units.
This value is preset to 5.000 m (or equivalent Units programmed).
The value entered automatically sets Span (P007) to the maximum recommended
value.
Values:
0.000 to 9999
P007
Span
Enter the maximum surface distance from Empty (P006).
Span is automatically preset to 1.1 x the blanking value (P800) less than the Empty
value (P006), unless it is altered manually.
For "distance" Operation (P001 = 3), Span is preset to the Empty value (P006).
Enter a lower value if desired. If the automatic setting is not high enough, mount the
transducer higher (see Installation Transducer Mounting) and enter the new Empty
(P006) distance.
Values:
0.000 to 9999
Note:
With the Quick Start Parameters altered as required, proceed to Operation to
identify / verify basic system performance.
Summary of Contents for AiRanger SPL PL-573
Page 1: ...AIRANGER SPL Instruction Manual PL 573 March 2001 IRANGER SPL 33455730 Rev 1 2 ...
Page 8: ...Page 8 AiRanger SPL PL 573 Specifications ...
Page 24: ...Page 24 AiRanger SPL PL 573 Installation ...
Page 86: ...Page 86 AiRanger SPL PL 573 Enhancement Param ...
Page 102: ...Page 102 AiRanger SPL PL 573 Maintenance ...
Page 108: ...Page 108 AiRanger SPL PL 573 Troubleshooting ...