PL-573
AiRanger SPL
Page 29
Quick Start Para
m.
Quick Start Parameters
Alter the Quick Start Parameters as required to suit installation requirements.
Note:
If the Quick Start Guide (PL-431) was used, proceed to Application Parameters
Refer to Technical Reference Application Examples for assistance, if required.
P001
Operation
Enter the type of RUN mode operation desired.
Select:
"level",
display Empty (P006) to material level distance .
"space",
display Span (P007) to material level distance.
"distance",
display transducer face to material level distance.
"out-of-service"the transducer is not fired, alarm relay(s) energize, pump relay(s) de-
energize, and mA output(s) go to the Empty vessel value.
Values:
0 = out-of-service
1 = level
2 = space
3 = distance (preset)
P002
Material
Enter the type of material to be monitored.
If the material presents a flat surface perpendicular to the transducer beam, select
liquid.
Values:
1 = liquid or flat surface (preset)
2 = solid
P003
Measurement Response
Enter how quickly the SPL is to respond to changing measurements.
Note:
Slower Measurement Response improves stability and reliability.
Values:
1 = slow ( 0.1 m / min )
2 = medium ( 1 m / min ) (preset)
3 = fast ( 10 m / min )
4 = surge ( 1.7 m / sec )
5 = immediate ( 17 m / sec )
Summary of Contents for AiRanger SPL PL-573
Page 1: ...AIRANGER SPL Instruction Manual PL 573 March 2001 IRANGER SPL 33455730 Rev 1 2 ...
Page 8: ...Page 8 AiRanger SPL PL 573 Specifications ...
Page 24: ...Page 24 AiRanger SPL PL 573 Installation ...
Page 86: ...Page 86 AiRanger SPL PL 573 Enhancement Param ...
Page 102: ...Page 102 AiRanger SPL PL 573 Maintenance ...
Page 108: ...Page 108 AiRanger SPL PL 573 Troubleshooting ...