Page 98
AiRanger SPL
PL-573
Technical Refer
e
nce
Communication Support
The SPL provides digital communication to a peripheral device, such as a computer
or PLC, in one of three modes via the communication port, terminals 26 through 32.
The mode of communication is established by the configuration of the connection
made at the SPL, RS-232, RS-485 or bipolar current loop.
The SPL utilizes
simplex convention
communication protocol. Data messages are
continuously transmitted at regular intervals (no poll is required) at 4800 baud. All
data is transmitted in structured messages of ASCII characters consisting of 8 data
bits, no parity, and 1 stop bit.
If Peripheral Communications (P740) is set for "formatted" messages, a comma is
inserted between each message field (except immediately preceding the "End of
Message" characters).
MT-00 Measurement Message
Field Name
Definition
Start Of Message
STX ($02)
Message Type
2 characters, 00 (indicates the following data pertains to a
scan point measurement)
Point #
3 characters, 001 to 003 (e.g. the message pertains to Point
Number 1)
Reading
5 characters, 0.000 to 9999. (e.g. reading = 678.9, DDDD. =
no data, EEEE. = overflow)
Status A
1 character, $0 to $F (convert to binary, e.g. temp, echo, and cable OK, not priority)
MSB
LSB
# # # #
1 = temp alarm
1 = loss of echo (failsafe expired)
1 = transducer cable fault
1 = priority point
start of message
point #
status A
status C
percent
end of message
temperature
status B
reading
message type
Summary of Contents for AiRanger SPL PL-573
Page 1: ...AIRANGER SPL Instruction Manual PL 573 March 2001 IRANGER SPL 33455730 Rev 1 2 ...
Page 8: ...Page 8 AiRanger SPL PL 573 Specifications ...
Page 24: ...Page 24 AiRanger SPL PL 573 Installation ...
Page 86: ...Page 86 AiRanger SPL PL 573 Enhancement Param ...
Page 102: ...Page 102 AiRanger SPL PL 573 Maintenance ...
Page 108: ...Page 108 AiRanger SPL PL 573 Troubleshooting ...