PL-573
AiRanger SPL
Page 63
Enhancement Param.
e.g. :
P711 = 2, material agitator
P712 = 5:2
A new reading will not be validated unless 5 consecutive measurements
higher or 2 consecutive measurements lower than the current readings occur.
Values:
x.y
x= # of `above' echoes
y = # of `below' echoes
Note:
Resetting P711 returns P712 to the respective preset values.
P713
Echo Lock Window
Use this feature to adjust the new measurement change permitted before Echo Lock
is applied.
The Echo Lock Window is a "time window" (in msec) placed about the echo used to
derive the Reading. When a new measurement falls within the window, the window is
recentered and the new Reading is calculated. Otherwise, the new measurement is
verified by Echo Lock (P711) before the SPL + updates the reading.
When "0" is entered (preset), the window is automatically calculated based on the
Max Fill / Empty Rate ( P700 / P701). This calculation is automatically performed
when Measurement Response (P003) is altered. See Technical Reference
Measurement Response.
For slower Measurement Response (P003) values the calculated Echo Lock Window
is narrow. For faster values the window becomes increasingly wider, (When
"immediate" is selected the window is normally wide open).
Values:
0.000 to 9999
Summary of Contents for AiRanger SPL PL-573
Page 1: ...AIRANGER SPL Instruction Manual PL 573 March 2001 IRANGER SPL 33455730 Rev 1 2 ...
Page 8: ...Page 8 AiRanger SPL PL 573 Specifications ...
Page 24: ...Page 24 AiRanger SPL PL 573 Installation ...
Page 86: ...Page 86 AiRanger SPL PL 573 Enhancement Param ...
Page 102: ...Page 102 AiRanger SPL PL 573 Maintenance ...
Page 108: ...Page 108 AiRanger SPL PL 573 Troubleshooting ...