Page 92
AiRanger SPL
PL-573
Technical Refer
e
nce
Example 1 - Level Measurement
Material Level
This is the most common application of the SPL level monitor.
For this example we'll assume the following:
•
one 30 m high cement silo is to be monitored.
•
the maximum vessel filling rate is 0.08 m per minute.
•
alarm indicators are required when the cement level exceeds 25 m or falls below 10
m.
•
filling equipment is to be automatically deactivated at 27 m.
•
in the event of a measurement difficulty, failsafe operation is to be activated in 2
minutes.
•
if the difficulty doesn't subside, the filling process is to be stopped before a spill
occurs.
•
an XLT-30 transducer is mounted with its face flush with the top of the vessel.
•
a TS-3 temperature sensor is connected to the Temp Sensor terminals.
27.00 m
(P103)
25.00 m
(P101)
10.00 m
(P102)
5.00 m
(P104)
29.01 m
(P007)
30.00 m
(P006)
transducer
Summary of Contents for AiRanger SPL PL-573
Page 1: ...AIRANGER SPL Instruction Manual PL 573 March 2001 IRANGER SPL 33455730 Rev 1 2 ...
Page 8: ...Page 8 AiRanger SPL PL 573 Specifications ...
Page 24: ...Page 24 AiRanger SPL PL 573 Installation ...
Page 86: ...Page 86 AiRanger SPL PL 573 Enhancement Param ...
Page 102: ...Page 102 AiRanger SPL PL 573 Maintenance ...
Page 108: ...Page 108 AiRanger SPL PL 573 Troubleshooting ...