Page 68
AiRanger SPL
PL-573
Enhancement Pa
ra
m.
SmartLinx
®
Parameters (P750 to P792)
Protocol Specific Parameters (P750-P789)
These parameters are specific to the SmartLinx
®
module installed. Refer to the
module documentation for a list and description of the specific parameter
requirements.
P790
Hardware Error
Use this feature to display the results of ongoing hardware tests within the
communications circuitry. If any test does not meet the PASS requirements,
communication halts and tests are repeated until PASS requirements are met.
Communications then resumes.
Displays:
PASS: no problem
FAIL: faulty SmartLinx module or SPL
ERR1: unknown protocol, upgrade the SPL software
P791
Bus Error
This feature indicates if an error condition is occurring on the bus.
Displays:
0 = no error
Ø
= error code, refer to the SmartLinx module documentation for explanation of the
error code
P792
Bus Error Count
This register increments by 1 each time a bus error (P752) is reported. The resister is
factory set at 0 and can be preset to any value. The register is reset to 0 by the
master reset (P999).