PL-573
AiRanger SPL
Page 99
Technical Refer
e
nce
Status B
1 character, $0 to $F (convert to binary, e.g. scan point is in high alarm)
MSB
LSB
# # # #
1 = low low alarm
1 = low alarm
1 = high alarm
1 = high high alarm
Status C
1 character, $0 to $F (convert to binary, e.g. scan point is not in rate or band alarm)
MSB
LSB
# # # #
1 = rate alarm 2
1 = rate alarm 1
1 = band alarm 1
1 = band alarm 2
Field Name
Definition
Temp
2 characters, $32 to $FA (convert to decimal and subtract
100, e.g. temperature = 20 °C)
Percent
5 characters, 00.00 to 9999. (e.g. current level = 85.00% of
span, EEEE. = field overflow)
End Of Message
CR ($0D)
MT-01 Hold Message
e.g.
Field Name
Definition
Start Of Message
STX ($02)
Message Type
2 characters, 01 (indicates the SPL was removed from the
RUN mode)
End Of Message
CR ($0D)
start of message
end of message
message type