MI 2892 Power Master
Technical specifications
194
6.2.22
Phase angle
Measuring range
Resolution
Accuracy
-180.0° ÷ 180.0°
0.1°
± 0.6°
6.2.23
400Hz systems specification
Sampling frequency:
Normal operation
12,2 kSamples/sec
Antialiasing filter
Passband (-3dB): 0 ÷ 5,7kHz
Stopband (-80dB): > 6,44 kHz
Sampling frequency:
Transients
49 kSamples/sec
Antialiasing filter
Passband (-3dB): 0 ÷ 24 kHz
Stopband (-80dB): > 26 kHz
Cycle aggregation:
50 cycles
6.2.24
VFD (Variable frequency drive) systems specification
Sampling frequency:
Normal operation
1,7 kSamples/sec
Antialiasing filter
Passband (-3dB): 0 ÷ 782 Hz
Stopband (-80dB): > 883 Hz
Sampling frequency:
Transients
49 kSamples/sec
Antialiasing filter
Passband (-3dB): 0 ÷ 24 kHz
Stopband (-80dB): > 26 kHz
Cycle aggregation:
5 cycles
6.2.25
Differences in specification between 400Hz, VFD and 50/60 Hz systems
Measurement / Recording
MI 2892 - 400Hz
MI 2892 - VFD
MI 2892 - 50 Hz / 60Hz
Voltage
•
(1)
•
(1)
•
Current
•
(1)
•
(1)
•
Frequency
335 Hz ÷ 465 Hz
5 Hz ÷ 110 Hz
•
Power
•
(1)
•
(1)
•
Energy
•
(1)
•
(1)
•
Unbalance
•
(1)
•
(1)
•
Flicker
-
-
•
THD
•
•
•
Voltage Harmonics
0 ÷ 13
th
0 ÷ 20
th
(3)
0 ÷ 50
th
Current Harmonics
0 ÷ 13
th
0 ÷ 20
th
(3)
0 ÷ 50
th
Voltage Interharmonics
-
0 ÷ 20
th
(3)
1 ÷ 50
th
Current Interharmonics
-
0 ÷ 20
th
1 ÷ 50
th
Events
•
(1)
•
(1)
•
RVC - Rapid Voltage Changes
-
•
(1)
•
Signalling
-
-
•
Network Configurations
•
(1)
•
(1)
•
General recorder
•
(1)
•
(1)
•