MI 2892 Power Master
Operating the instrument
67
Record
Record start
Record stop
Trigger point
Pre-trigger
Post-trigger
Figure 3.47: Triggering in waveform record
3.15.1
Setup
By entering WAVEFORM RECORDER from the RECORDERS submenu the following setup screen is shown:
Figure 3.48: Waveform recorder setup screen
Table 3.56: Waveform recorder settings description and screen symbols
Waveform recorder is active, waiting for trigger
Waveform recorder is active, recording in progress
Trigger
Trigger source set up:
Events – triggered by voltage event (see 3.21.2);
Alarms – triggered by alarm activation (see 3.21.3);
Events & Alarms – triggered by alarm or event;
Level U – triggered by voltage level;
Level I – triggered by current level (inrush).
Interval – periodical trigger for given time period (each 10
minutes for example).
Level*
Voltage or current level in % of nominal voltage or current and in (V
or A), which will trigger recording
Slope*
Rise – triggering will occur only if voltage or current rise
above given level
Fall - triggering will occur only if voltage or current fall below
given level
Any – triggering will occur if voltage or current rise above or
fall below given level
Duration
Record length.
Pretrigger
Recorded interval before triggering occurs.
Interval
Interval between two time triggered waveforms in Interval trigger
type
Store mode
Store mode setup:
Single – waveform recording ends after first trigger;