MI 2892 Power Master
Operating the instrument
65
Note: If during record session instrument batteries are drained, due
to long interruption for example, instrument will shut down
automatically. After power restauration, it will automatically start
new recording session.
Include Voltage events (with waveform) or Include Alarms (with
waveform) option is selected. Icon show that waveform recorder is
active, waiting for trigger
Voltage event or alarm waveform recorder is active, waveform
recording is in progress
Profile
Select recording profile:
Standard profile. Include all measurement in record.
Suitable for most PQ measurement
Limited profile. Include limited set of measurements (most
important). Suitable for long records with short interval (1
week record with 1 second interval). See section 4.4 for
details.
Include events
Select whether events are included in the record.
On: Record events signatures in table form (see 3.17 for
details)
On (with waveforms): Records events signatures in table
form and capture event waveform using Waveform recorder
with Event type trigger and set duration defined in
Waveform recorder setup screen (see 5.1.13 for details).
Off: Events are not recorded
Include alarms
Select whether alarms are included in the record.
On: Record alarm signatures in table form (see 3.18 for
details)
On (with waveforms): Records alarm signatures in table
form and capture alarm waveform by using Waveform
recorder with Alarm type trigger and set duration defined in
Waveform recorder setup screen (see 5.1.14 for details).
Off: Alarms are not recorded
Include signalling events
Select whether signalling events according to the IEC 61000-4-30
should be included in the record.
On: Signalling events included in the record
Off: Signalling events are not recorded
Start time
Define start time of recording:
Manual, pressing function key F1
At the given time and date.
Duration
Define recording duration. General recorder will record
measurement for given time duration:
Manual,
1, 6 or 12 hours, or
1, 2, 3, 7, 15, 30, 60 days.
Recommended/maximal
record duration:
Show recommended and maximal Duration parameter for giver
recording Interval.
Available memory
Show SD card free space