MI 2892 Power Master
Technical specifications
197
Trigger
Voltage or current level, voltage events, alarms defined in alarm table or
manual trigger.
6.3.3
Waveform snapshot
Sampling
7 kSamples/s, continuous sampling per channel. All channels are sampled
simultaneously.
Recording time
10/12 cycle period.
Recording
quantities
Waveform samples of: U
1
, U
2
, U
3
, U
N
, (U
12
, U
23
, U
31
), I
1
, I
2
, I
3
, I
N
,
all measurements.
Trigger
Manual
6.3.4
Transients recorder
Sampling
49 kSamples/s, continuous sampling per channel. All channels are sampled
simultaneously.
Recording time
From 1 ÷ 50 cycle period.
Recording
quantities
Waveform samples of: U
1
, U
2
, U
3
, U
N
, (U
12
, U
23
, U
31
), I
1
, I
2
, I
3
, I
N
Calculated for all channels: U
RMS
, I
RMS
, THD
U
, THD
I
Trigger:
Manual, dV - for details see section 5.1.20