MI 3325 MultiServicerXD
87
Custom value is selected from the list.
Example of on-screen numeric keyboard
– direct H
Limit custom value entry.
Apply option selection from Limit Calculator options
bar automatically overwrite H Limit(R) parameter of
selected
single
test
-
Continuity
or
PE_conductor(PRCD).
6.2.3 Insulation resistance RPAT (Portable appliance)
Figure 6.25: Insulation resistance (Portable appliance) test menus
Test results / sub-results
Riso
......... Insulation resistance
Riso-S
...... Insulation resistance-S
Um
........... Test voltage
Test parameters
Type
Type of test
[Riso, Riso-S, (Riso, Riso-S)]
Uiso
Nominal test voltage [250 V, 500 V]
Duration
Duration
[Off, 2 s
… 180 s]
Test limits
L limit(Riso)
Low limit (Riso) [Off, 0.0
1 MΩ … 10.0 MΩ ]
L limit(Riso-S)
Low limit (Riso-S) [Off, 0.10 M
Ω … 10.0 MΩ ]
Test circuits
Figure 6.26: Insulation resistance Riso (socket)