MI 3325 MultiServicerXD
122
STEP 2: Measuring the Voltage drop
Enter the
Voltage Drop
function.
Set test parameters / limits.
Connect test cable to the instrument.
Connect 3-wire test lead or Plug test cable to the tested points, see
Start the measurement.
Save results (optional).
Figure 6.85: Examples of measurement result: Zref (Step 1, left figure) and Voltage drop
(Step 2)
6.2.23 Rpe
– PE conductor resistance
Figure 6.86: PE conductor resistance measurement menu
Test results / sub-results
Rpe
PE conductor resistance
Test parameters
Bonding
[Rpe, Local]
RCD
[Yes, No]
Test limits
Limit(Rpe)
Max. resistance [Off, 0.
1 ... 20.0 Ω]