MI 3325 MultiServicerXD
Appendix B
188
6.2.21 Z auto - Auto test sequence for fast line and loop
Test parameters
Fuse Type
Selection of fuse type [gG, NV, B, C, D, K, Off, Custom]
Isc factor
Correction factor Isc
[0.2 … 3.0]
Test limits
Ia(Ipsc)
Minimum fault current for selected fuse
are replaced with
Test parameters
Fuse Type
Selection of fuse type [B, C, D, Fuse, Off, Custom]
Z factor
Z factor
[1, 1.04]
Test limits
Zlim(Z)
Zlim(Z (LPE), Z (LN))
Maximum loop / line impedance for selected fuse or custom value.
Figure B.4: Examples of Z line, Z loop and Z auto measurement result
Prospective fault / short circuit current I
PSC
is calculated from measured impedance as follows:
Z
U
I
N
PSC
Loop / line impedance limit Z
Lim(Z)
for selected fuse is calculated from the following formula:
Lim
Z
Lim
Z
factor
Scaling
Z
_
)
(
where:
Zlim .......................... Maximum loop / line impedance for selected fuse
Scaling factor ............ Impedance correction factor (Z factor)
Un ............................. Nominal U
L-PE
voltage
Added new test parameter and sub-result:
Test parameter
Random phase
[No, Yes]
Test results / sub-results
Phase
Starting phase (if Random phase parameter is enabled)