MI 3325 MultiServicerXD
Appendix B
184
B.2
Profile Hungary (AUAE)
Fuse type gR added to the fuse tables. Refer to
Fuse tables guide
for detailed information on
fuse data.
Modifications in chapter
Added tests with multiplication factor 2.
Modification of RCD Auto test procedure
RCD Auto test inserted steps
Notes
Re-activate RCD
.
Test with 2
I
N
, (+) positive polarity (new step 3).
RCD should trip-out
Re-activate RCD
.
Test with 2
I
N
, (-) negative polarity (new step 4).
RCD should trip-out
Inserted new Step 3
Inserted new Step 4
Figure B.1: Example of individual steps in RCD Auto test
– Inserted 2 new steps
Test results / sub-results
t I∆N x1 (+)
Step 1 trip-out time (I
=I
N
, (+) positive polarity)
t I∆N x1 (-)
Step 2 trip-out time (I
=I
N
, (-) negative polarity)
t I∆N x2 (+)
Step 3 trip-out time (I
=2
I
N
, (+) positive polarity)
t I∆N x2 (-)
Step 4 trip-out time (I
=2
I
N
, (-) negative polarity)
t I∆N x5 (+)
Step 5 trip-out time (I
=5
I
N
, (+) positive polarity)
t I∆N x5 (-)
Step 6 trip-out time (I
=5
I
N
, (-) negative polarity)
t I∆N x0.5 (+)
Step 7 trip-out time (I
=½
I
N
, (+) positive polarity)
t I∆N x0.5 (-)
Step 8 trip-out time (I
=½
I
N
, (-) negative polarity)
I∆ (+)
Step 9 trip-out current ((+) positive polarity)
I∆ (-)
Step 10 trip-out current ((-) negative polarity)
Uc
Contact voltage for rated I
N
B.3
Profile Finland (AUAG)
Ia(Ipsc) limit modified in fuse types gG, NV, B, C, D and K.
Refer to
Fuse tables guide
for detailed information on fuse data.