MI 3325 MultiServicerXD
24
Warning
!
A very high voltage is / will be present on the instrument output.
Warning!
Dangerous voltage on TP1-PE input! Stop the activity immediately
and eliminate the fault / connection problem before proceeding with any
activity!
Continuous sound warning and yellow coloured screen is also present.
RCD tripped-out during the measurement (in RCD functions).
High electrical noise was detected during measurement. Results may be
impaired.
L and N are changed.
In most instrument profiles L and N test terminals are reversed automatically
according to detected voltages on input terminal. In instrument profiles for
countries where the position of phase and neutral connector is defined the
selected feature is not working.
Single fault condition in IT system.
Measurement can’t be started. 3 phase adapter should be disconnected from
the instrument.
Measurement in combination with appropriate 3 phase adapter can be carried
out.
The measurement can be carried out only in combination with appropriate 3
phase adapter.
Use A 1143 Euro Z 290 A adapter for this test.
Measurement is running, consider displayed warnings.
Count down timer (in seconds) within measurement.
4.5.3 Result indication
Measurement result is inside pre-set limits (PASS).
Measurement result is out of pre-set limits (FAIL).
Measurement is aborted. Consider displayed warnings and messages.
RCD t and RCD I measurements will only be performed if the contact
voltage in the pre-test at nominal differential current is lower than the set
contact voltage limit!