MI 2792 PowerQ4 Plus
Operating the instrument
43
Figure 3.32: Basic recorder setup screen
In following table description of recorder settings is given:
Table 3.38: Recorder settings description
Record Type
Select type of recording. Following options are
available and can be set by using configuration menu:
Record (user defined)
Voltage quality (according to EN 50160)
Interval
Select recorder aggregation interval. For each time
interval minimal, average and maximal value will be
recorded (for each signal). The smaller the interval is,
more measurements will be used for the same record
duration.
Note:
The instrument automatically changes the duration
in case there is not enough memory for the desired
interval and duration.
Note:
EN 50160 record type stores only average values
per interval.
Signals
Select signals to record. See 4.2.5 for detail channel list.
U, I, f – select voltage, current and freq. parameters
for recording.
Power & Energy – select power and energy
parameters for recording.
Flickers – select flicker parameters for recording.
Sym – select unbalance parameters for recording.