MI 2792 PowerQ4 Plus
Technical specifications
128
With A 1033
1000 A
000,000,000.001 ÷ 999,999,999.999
±1.6 %
eS
*Accuracy values are valid if cos
φ
0.80, I
10 % I
Nom
and U
80 % U
Nom
**Accuracy values are valid if sin
φ
0.50, I
10 % I
Nom
and U
80 % U
Nom
***Accuracy values are valid if cos
φ
0.50, I
10 % I
Nom
and U
80 % U
Nom
6.2.11 Voltage harmonics and THD
Measuring range
Resolution Accuracy
Uh
N
< 3 % U
Nom
10
mV
± 0.15 %
U
Nom
3 % U
Nom
< Uh
N
< 20 % U
Nom
10 mV
± 5 %
Uh
N
U
Nom
: nominal voltage (RMS)
Uh
N
: measured harmonic voltage
N
:
harmonic component 1
st
÷ 50
th
Measuring range
Resolution Accuracy
0 % U
Nom
< THD
U
< 20 % U
Nom
0.1 %
± 0.3
U
Nom
: nominal voltage (RMS)
6.2.12 Current harmonics and THD
Measuring range
Resolution Accuracy
Ih
N
< 10 % I
N
om
10
mV
± 0.15 %
I
Nom
10 % I
N
om
< Ih
N
< 100 %
10 mV
± 5 %
Ih
N
I
N
om
: Nominal
current
(RMS)
Ih
N
: measured harmonic current
N
:
harmonic component 1
st
÷ 50
th
Measuring range
Resolution Accuracy
0 % I
N
om
< THD
I
< 100 % I
N
om
0.1 %
± 0.6
100 % I
N
om
< THD
I
< 200 % I
N
om
0.1 %
± 1.5
I
N
om
: Nominal
current
(RMS)
6.2.13 Voltage interharmonics
Measuring range
Resolution Accuracy
Uih
N
< 3 % U
Nom
10
mV
± 0.15 %
U
Nom
3 % U
Nom
< Uih
N
< 20 % U
Nom
10 mV
± 5 %
Uih
N
U
Nom
: nominal voltage (RMS)
Uih
N
: measured harmonic voltage
N
:
interharmonic component 1
st
÷ 50
th
6.2.14 Current interharmonics
Measuring range
Resolution Accuracy
Ih
N
< 10 % I
N
om
10
mV
± 0.15 %
I
Nom
10 % I
N
om
< Ih
N
< 100 %
10 mV
± 5 %
Iih
N
I
N
om
: Nominal
current
(RMS)
Iih
N
: measured interharmonic current
N
:
interharmonic component 1
st
÷ 50
th