MI 2792 PowerQ4 Plus
Technical specifications
127
Excluding clamps
0.000 k ÷ 999.9 M
±0.5 %
S
With A 1227
Flex clamps
0.000 k ÷ 999.9k
±1.8 %
S
With A 1281
Multirange clamps 100 A
0.000 k ÷ 999.9k
±0.8 %
S
Apparent power
S***
With A 1033
1000 A
000.0 k ÷ 999.9 k
4 digits
±1.6 %
S
*Accuracy values are valid if cos
φ
0.80, I
10 % I
Nom
and U
80 % U
Nom
**Accuracy values are valid if sin
φ
0.50, I
10 % I
Nom
and U
80 % U
Nom
***Accuracy values are valid if cos
φ
0.50, I
10 % I
Nom
and U
80 % U
Nom
6.2.8 Power factor (Pf)
Measuring range
Resolution
Accuracy
-1.00 ÷ 1.00
0.01
± 0.02
6.2.9 Displacement factor (Cos
φ
)
Measuring range
Resolution
Accuracy
0.00 ÷ 1.00
0.01
± 0.02
6.2.10 Energy
Measuring
range
(kWh, kVArh, kVAh)
Resolution Accuracy
Excluding clamps
000,000,000.001 ÷ 999,999,999.999
±0.5 %
eP
With A 1227
Flex clamps
000,000,000.001 ÷ 999,999,999.999
±1.8 %
eP
With A 1281
Multirange clamps
100
000,000,000.001 ÷ 999,999,999.999
±0.8 %
eP
Active energy eP*
With A 1033
1000 A
000,000,000.001 ÷ 999,999,999.999
12 digits
±1.6 %
eP
Excluding clamps
000,000,000.001 ÷ 999,999,999.999
±0.5 %
eQ
With A 1227
Flex clamps
000,000,000.001 ÷ 999,999,999.999
±1.8 %
eQ
With A 1281
Multirange clamps
100
000,000,000.001 ÷ 999,999,999.999
±0.8 %
eP
Reactive energy
eQ**
With A 1033
1000 A
000,000,000.001 ÷ 999,999,999.999
12 digits
±1.6 %
eQ
Excluding clamps
000,000,000.001 ÷ 999,999,999.999
±0.5 %
eS
With A 1227
Flex clamps
000,000,000.001 ÷ 999,999,999.999
±1.8 %
eS
Apparent
energy eS*
**
With A 1281
Multirange clamps
100
000,000,000.001 ÷ 999,999,999.999
12 digits
±0.8 %
eP