MI 2792 PowerQ4 Plus
Technical specifications
130
6.3 Recorders
6.3.1 General recorder
Sampling
5 readings per second, continuous sampling per channel. All
channels are sampled simultaneously. Sampling frequency is
continuously synchronized with main frequency.
Recording time From 30 min with 1 second display resolution up to 99 days with 1
hour display resolution.
Recording type
Linear
– start and stop in accordance to user settings.
Circular
– when recorded data exceeds free memory, oldest data
in the current recording are overwritten with the new one.
Recording
quantities
1 ÷ 524 parameters can be recorded. For each parameter
minimum, maximal average and active average value is stored.
For default recorder settings (179 signals selected for recording)
Resolution
1 s
3 s
5 s
10 s
1 min
2 min
Duration
1 hr
4 hrs
7 hrs
15 hrs
3 days
7 days
Resolution
5 min
10 min
15 min
30 min
60 min
Duration
18 days 37 days 56 days
99 days 99 days
Events
Up to 1000 voltage events signatures can be stored into record
Alarms
Up to 1000 alarms signatures can be stored into record
Trigger
Start time or manual
6.3.2 Waveform recorder
Sampling
102.4 samples per cycle period, continuous sampling per
channel. All channels are sampled simultaneously. Sampling
frequency is continuously synchronized with mains frequency.
Recording time From 10 cycle period to 3770 cycle periods
Recording type
Single
– waveform recording ends after first trigger.
Continuous
– consecutive waveform recording until user stops
the measurement or instrument runs out of storage memory.
Recording
quantities
Waveform samples of: U
1
, U
2
, U
3
, U
N
, (U
12
, U
23
, U
31
), I
1
, I
2
, I
3
, I
N
For 50 Hz mains frequency
No. of signals
1 2 4
8
Duration
75 sec
38 sec
19 sec
9 sec
Trigger:
Voltage event, alarms defined in alarm table or manual
6.3.3 Inrush/fast recorder
Sampling
1 reading per half-cycle ÷ 1 reading per 10-cycles
(for 50 Hz mains frequency: 5 to 100 readings per second)
All channels are sampled simultaneously. Sampling frequency is
continuously synchronized with mains frequency.
Recording time From 1 s ÷ 3 min
Recording type
Single
– inrush recording ends after first trigger
Continuous
– consecutive inrush recording until user stops the
measurement or instrument runs out of storage memory.
Recording U
1Rms(1/2)
, U
2Rms(1/2)
, U
3Rms(1/2)
, U
NRms(1/2)
, (U
12Rms(1/2)
, U