MI 2792 PowerQ4 Plus
Technical specifications
124
NOTE:
Instrument has 3 voltage ranges. Range has to be chosen according to the
network nominal voltage, according to the table bellow.
Nominal phase voltage: U
Nom
Recommended Voltage range
50 V ÷ 110 V
Voltage Range 1: 50 V ÷ 110 V (L-N)
110 V ÷ 240 V
Voltage Range 2: 110 V ÷ 240 V (L-N)
240 V ÷ 1000 V
Voltage Range 3: 240 V ÷ 1000 V (L-N)
Nominal phase-to-phase voltage:
U
Nom
Recommended Voltage range
86 V ÷ 190 V
Voltage Range 1: 86 V ÷ 190 V (L-L)
190 V ÷ 415 V
Voltage Range 2: 190 V ÷ 415 V (L-L)
415 V ÷ 1730 V
Voltage Range 3: 240 V ÷ 1730 V (L-L)
NOTE:
Assure that all voltage clips are connected during measurement and logging
period. Unconnected voltage clips are susceptible to EMI and can trigger false events. It
is advisable to short them with instrument neutral voltage input.
6.2.2 Phase Voltages
U
pRms
, p: [1, 2, 3, 4, N]
Measuring range
Resolution Accuracy
Crest factor
Range 1: 20.00 V
RMS
÷ 150.00 V
RMS
10
mV
Range 2: 50.0 V
RMS
÷ 360.0 V
RMS
Range 3: 200.0 V
RMS
÷ 1500.0 V
RMS
100 mV
± 0.2 %
U
RMS
min 1.5
U
pRms(1/2)
p: [1, 2, 3, 4, N], AC+DC
Measuring range
Resolution Accuracy
Crest factor
Range 1: 20.00 V
RMS
÷ 150.00 V
RMS
Range 2: 50.00 V
RMS
÷ 360.00 V
RMS
Range 3: 200.00 V
RMS
÷ 1500.00 V
RMS
10 mV
± 0.5 %
U
RMS
min 1.5
Cf
Up
, p: [1, 2, 3, 4, N], AC+DC
Measuring
range Resolution
Accuracy
1.00 ÷ 2.50
0.01
± 5 % ·
Cf
U
U
pPk
: p: [1, 2, 3, 4, N], AC+DC
Measuring range
Resolution
Accuracy
Range 1: 20.0 V ÷ 255.0 Vpk
± 0.5 % ·
U
Pk
Range 2: 50.0 V ÷ 510.0 Vpk
± 0.5 %
·
U
Pk
Range 3: 200.0 V ÷ 2250.0 Vpk
100 mV
± 0.5 %
·
U