MI 2792 PowerQ4 Plus
Technical specifications
123
6 Technical specifications
6.1 General specifications
Working temperature range:
-10
C ÷ +50
C
Storage temperature range:
-20
C ÷ +70
C
Max. humidity:
95 % RH (0
C ÷ 40
C), non-condensing
Pollution degree:
2
<
double insulation
Over voltage category:
CAT IV / 600 V; CAT III / 1000 V
Protection degree:
IP 42
Dimensions:
(220 x 115 x 90) mm
Weight (without accessories):
0.65 kg
Display:
Graphic liquid crystal display (LCD) with backlight,
320 x 200 dots.
Memory:
8 MB Flash
Batteries:
6 x 1.2 V NiMh rechargeable batteries
type HR 6 (AA)
Provide full operation for up to 15 hours*
External DC supply:
12 V, 1.2 A min
Maximum power consumption:
150 mA – without batteries
1
A – while charging batteries
Battery charging time:
4 hours *
USB 1.0
Standard USB Type B
2400 baud ÷ 921600 baud
Communication:
RS232
8 pin PS/2 – type
2400 baud ÷ 115200 baud
* The charging time and the operating hours are given for batteries with a nominal
capacity of 2500mAh
6.2 Measurements
Note:
In order to get resolution and accuracy specified in this section, measuring data
should be observed by PowerView v2.0 (Waveform Snapshoot or On-Line View).
PowerQ4 Plus display resolution is reduced due to screen space constraints and
enhanced visibility of presented measurements (larger screen fonts and space between
measurements).
6.2.1 General description
Max. input voltage (Phase – Neutral):
1000 V
RMS
Max. input voltage (Phase – Phase):
1730 V
RMS
Phase - Neutral input impedance:
6 M
Ω
Phase – Phase input impedance:
6 M
Ω
AD converter
16 bit 8 channels,
simultaneous sampling
Reference temperature
23
°
C ± 2 °C
Temperature influence
60 ppm/
°
C