IMPULSE
®
•G+ Mini Technical Manual
November 2020
Page 96
3A Trm A1/A2 Enable
Multi-function analog input A1/A2 Enable/Disable.
When programmed, analog input A1/A2 is enabled
by ON.
-
3F Fault Reset
Reset by ON
-
40 Fast Stop N.O.
Input On = Decel to stop via fast stop time B05.08
42 Fast Stop N.C.
Input Off = Decel to stop via fast stop time B05.08
43 Timer Enable
Function settings by C12.03, C12.04. It is set with
timer function output [Multi-Function Output]
47 Analog Hold
Analog frequency reference Sample/Hold
-
4C DCInj Braking
ON: DC injection braking command, once SFS
reaches Zero Speed
-
53 Comm Test
Communication test mode - loopback test of
modbus RS-422/485
-
55 Drive Enable
When programmed, must be ON in order for
Inverter Ready - Generates “Drive not Ready”.
“DNE” is displayed.
-
56 Klixon N.O.
When Closed, Reset run command, use stopping
method B03.03, display oL8 - Klixon Alarm on
Keypad
57 Klixon N.C.
When Open, Reset run command, use stopping
method B03.03, display oL8- Klixon Alarm on
Keypad
58 Brake Answer back Generates BE0, BE4, BE5, alarm or fault conditions
(C08.04, C08.11)
59 Alternate Upper
Frequency
Alternate Reference Upper Limit Frequency
5A Maintenance Reset Reset Maintenance Timer (C12.05 - C12.06,
U01.52)
5B BE6 Up Speed Limit Limit Fref to C08.17 (BE6 Up Speed Limit)
5F Phantom Fault N.C. Stops motion based C03.09 but does not change
Keypad display. Stop L.E.D. on JVOP blinks
62 Weight Limit N.O.
Weighted Upper Limit (UL3). Stopping Method
determined by C03.08
63 Phantom Fault N.O. Stops motion based C03.09 but does not change
Keypad display. STOP L.E.D. on JVOP blinks
65 Dwell Enable
Enables/Disables Dwell function.
69 LC Disable
Input On = Load Check disabled.
-
70 Torque Detection
Overtorque/Undertorque detection is enabled and
disabled by MFDI. When the input is closed,
Overtorque/Undertorque detection is enabled
-
80 Forward Run
Forward Run Command
-
81 Reverse Run
Reverse Run Command
-
Parameter
Name
Function
Page Range
Default
* Parameter defaults changed by X-Press Programming