5.6.5 Analog Output
The IMPULSE
®
•G+Mini has one analog output for the external monitoring of VFD conditions.
12 Regen Torque Limit
15 FWD/REV Torque Limit
1F Not Used
H03.11
Terminal A2 Gain
Gain multiplier for terminal A2 analog input signal
-999.9–999.9%
100.0
H03.12
Terminal A2 Bias
Bias multiplier for terminal A2 analog input signal
-999.9–999.9%
000.0
H03.13
Analog Input Filter Time
Constant
Analog input filter average time; analog delay time
constant between Terminals A1 and A2
0.00-2.00sec
0.03
Parameter
Name
Function
Range
Default
H04.01
Terminal AM Select
Assigns one of the following functions for analog
output Terminal AM.
0–154
102
0 Not Used
101 Frequency Reference
102 Output Frequency
103 Output Current
105 Motor Speed (OLV only)
106 Output Voltage
107 DC Bus Voltage
108 Output Power
109 Torque Reference (OLV
only)
115 Term A1 Level
116 Term A2 Level
120 SFS Output
154 Input Pulse Monitor
H04.02
Terminal AM Gain
Gain multiplier for Terminal AM analog output signal
-999.9–999.9%
100.0
H04.03
Terminal AM Bias
Bias multiplier for Terminal AM analog output signal
-999.9–999.9%
000.0
Parameter
Name
Function
Range
Default