IMPULSE
®
•G+ Mini Technical Manual
November 2020
Page 165
L06.08
Mechanical Weakening Detection
Selection
00
00–08
-
00: Disabled
01: Speed (signed) > L06.09; Continue
Running (Alarm)
02: Speed (unsigned) > L06.09;
Continue
Running (Alarm)
03: Speed (signed) > L06.09; Stop
(Protection)
04: Speed (unsigned) > L06.09; Stop
(Protection)
05: Speed (signed) < L06.09; Continue
Running (Alarm)
06: Speed (unsigned) < L06.09;
Continue
Running (Alarm)
07: Speed (signed) < L06.09; Stop
(Protection)
08: Speed (unsigned) < L06.09; Stop
(Protection)
L06.09
Mechanical Weakening Detection Level
110.0
-110.0–110.0
%
L06.10
Mechanical Weakening Detection Time
0.1
0.0–10.0
sec
L06.11
Mechanical Weakening Start Time
0
0–65535
hrs
L08.02
Overheat Pre-Alarm Level
95
50–130
°C
L08.03
Overheat Pre-Alarm Selection
05
00–05
-
00: Decel to Stop
01: Coast to Stop
02: Fast Stop
03: Use B03.03 Stopping Method
04: Alarm Only
05: Derated Operation (L08.19)
L08.05
Input Phase Loss Selection
01
00–01
-
00: Disabled
01: Enabled
L08.06
Input Phase Loss Detection Level
(Increasing L08.06 from default value
may cause DC BUS capacitor failure)
5.0
0.0–5.0
%
L08.07
Output Phase Loss Selection
01
00, 01
-
00: Disabled
01: Enabled
L08.08
Output Phase Loss Detection Level
5.0
0.0–20.0
%
Parameter
Parameter Name
Default
Range
Units
Page