IMPULSE
®
•G+ Mini Technical Manual
November 2020
Page 163
L02.07
Power-loss Ride Thru Accel
0.0
0.0–25.5
sec
L03.01
Stall Prevention Accel Select
00: Disabled
01: General Purpose
02: Intelligent
01
00–02
-
L03.02
Stall Prevention Accel Level
150
0–150
%
L03.03
Stall Prevention Constant HP Limit
50
0–100
%
L03.05
Stall Prevention Run Select
00: Disabled
01: Decel Time 1
02: Decel Time 2
01
00–02
-
L03.06
Stall Prevention Run Level
150
30–150
%
L03.17
DC Bus Voltage for Intelligent Control
370
150–400
V
L03.20
Main Circuit Voltage Gain
A01.02
0.00–5.00
-
-
L03.21
Deceleration Calculation Gain
A01.02
0.00–200.00
-
-
L03.23
Automatic Stall Prevention Selection
During Run
00
00–01
-
00: Sets the level to L03.04
throughout the entire frequency
range
01: Automatically lowers Stall
Prevention level during run in the
constant power range. The lower
limit will be 40% of L03.06.
L03.24
Motor Acceleration Time Inertial
Calculations
O02.04
0.001–10.000
-
L03.25
Load Inertia Ratio
1.0
0.0–1000.0
-
L04.01
Speed Agree Level
0.0
0.0–150.0
Hz
L04.02
Speed Agree Width
2.0
0.0–20.0
Hz
L04.03
Speed Agree Level ±
0.0
-150.0–150.0
Hz
L04.04
Speed Agree Width ±
2.0
0.0–20.0
Hz
L04.07
Speed Agree Detection
00: No detection during baseblock
01: Detection always enabled
00
00, 01
-
Parameter
Parameter Name
Default
Range
Units
Page