Page 60
5.1.3.8
LOC/REM Run Select
If the run reference/speed reference are switched between serial mode and terminal mode, B03.07 determines
action after the switch.
Parameter
Name
Function
Range
Default
B03.07
LOC/REM Run Sel
Determines action after switching Run/Speed
reference source.
00–01
00
00 Cycle Extrn Run
If the run command is present at the time when
Run/Speed reference source is switched, it
requires the run command to be removed and then
reapplied from the new source to resume the
normal operation.
01 Accept Extrn RUN
If the run command is present at the time when the
Run/Speed reference source is switched, it does
not require the run command from the new source
to be removed. The normal operation will continue.
B03.10
Allow Run at Power UP
Determines whether a run command, enabled on
VFD power up, will run the motor. When disabled,
a new run command is required before the motor
will run.
00–01
00
00 Disabled
01 Enabled
Parameter
Name
Function
Range
Default
B03.15
Reference Source 2 Selection
Selects frequency reference source when
H01.xx = 1F.
00–04
01
00 Keypad
Keypad
01 Terminals
Control circuit terminal
02 Modbus Communication
Modbus Serial Communication
03 Option PCB
Industrial Communication
04 Pulse Input
Pulse Input (Terminal RP)
B03.16
Run Source 2 Selection
Selects run command source when H01.xx = 1F.
00–03
01
00 Keypad
Keypad
01 Terminals
Control circuit terminal
02 Modbus Communication
Modbus Serial Communication
03 Option PCB
Industrial Communication