IMPULSE
®
•G+ Mini Technical Manual
November 2020
Page 91
5.5.2 Profibus-DP Communication Option Card Setup
Settings for the Profibus-DP communication option card SI-P3.
Parameter
Name
Function
Range
Default
F06.01
Comm Bus Fault (BUS)
Stopping method when a BUS fault occurs
00-04
01
00 Decel to Stop
01 Coast to Stop
02 Fast-Stop
03 Use B03.03 Method
04 Alarm Only
05 Decel to Stop (Auto Reset)
06 Coast to Stop (Auto Reset)
07 Fast-Stop (Auto Reset)
08 Use B03.03 Method (Auto Reset)
F06.02
Comm External Fault (EF0)
External Fault (EF0) detection method via
Profibus-DP
00-01
00
00 Always Detected
01 Only During Run
F06.03
EF0 Fault Action
Stopping method when an EF0 fault occurs
00-04
01
00 Decel to Stop
01 Coast to Stop
02 Fast-Stop
03 Use B03.03 Method
04 Alarm Only
F06.08
Comm Parameter
Initalization
Determines whether communication-related
parameters (F06.xx and F07.xx) are reset
when the VFD is initialized with A01.05.
00-01
00
00 Initalize Comm Parameters
01 Don't Initialize Comm Parameters
F06.14
BUS Fault Auto Reset
Determines whether a BUS fault will be
automatically reset.
00-01
00
00 Disabled
01 Enabled
F06.30
Profibus Node Address
Sets the node address for Profibus-DP
communications.
0-125
00
F06.31
Profibus Clear Select
Determines the operation when a “Clear
Mode” command is received on the Profibus-
DP option card.
00-01
00
00 Reset to Zero
01 Hold Previous Value