DL30-G USERS MANUAL EM-8571-G Rev.2
(3) Set the [CH setting] as [SLMP], and enter the parameters referring to the table below.
Parameter
Description
Slave No.
Enter the slave No. (0 to 31) set in (1).
SLMP device
Choose the device code of the SLMP device to be connected.
SLMP device No.
Set the device No. of the SLMP device to be connected.
PI data is 32 bit data set in two addresses.
When setting 16 bit devices, set the device of the smaller device No., and check
or uncheck the [Invert] check box depending on the order of high/low devices.
Measuring mode
(Modbus/TCP·SLMP)
Set the type of the 32 bit data read from the remote I/O. Select from the follow-
ing.
• Accumulation
The cumulative total is calculated by accumulating the difference between the
value at the start of cumulative totalizing and the value when it is reset, for each
sampling duration.
This corresponds to the cumulative total data of the SLMP device.
• Actual value
The retrieved data is recognized as a signed 32 bit integer, and its value is taken
as sampling data.
This corresponds to the power data of the SLMP device.
• Float
The retrieved data is recognized as single precision floating point, and its value
is taken as sampling data.
This corresponds to the power data of the SLMP device.
Pulse range
Set the same value as the pulse range set in the SLMP device.
For details, see the Users Manual for the SLMP device.
Settable only for the Accumulation.
Filter
Select the filter function from None / Moving average / Delay buffer.
Selectable only for the actual (engineering unit) values.
1. Select
2. Enter
3. Enter