DL30-G USERS MANUAL EM-8571-G Rev.2
Assigning remote I/O to DI
(1) First, perform the I/O slave setting for the remote I/O device.
➔
(2) Click [Discrete input (DI)] button in the [Input/Output] window to display the [Discrete input (DI)].
Double-click a row of the DI channel to be set in this window to display the [DI setting] window.
(3) Set the [CH setting] as [Modbus/TCP], and enter the [Slave No.], [Modbus/TCP register type], and
[Modbus/TCP register address].
Parameter
Description
Slave No.
Enter the slave No. (0 to 31) set in (1).
Modbus/TCP register type
Select between [Coil (0X)] and [Input (1X)].
Modbus/TCP register address
Set the register address in the above register type (1 to 65536).
Input/Output
Discrete input (DI)
1. Click
DI setting
2. Double-click
1. Select