128
DL30-G USERS MANUAL EM-8571-G Rev.2
I/O mapping (DO)
I/O mapping function is used to connect between DI and DO, and MD and DO so that an input is copied as an
output.
(1) Set [Type] and [CH] for [I/O mapping] in the [DO setting window].
DO setting
Enter
(2) Set [Type] and [CH] referring to the following table.
Parameter
Description
Type
Choose DI or MD.
CH
Specify a discrete input channel.
Use the above procedure to set all the CHs.
The CH setting for which the setting is complete in the [Discrete output (DO)] window can also be copied to
other CHs and only the required portions can be edited.
➔
NOTES
Channels assigned for I/O mapping function cannot be controlled on the web browser and the
scheduling function, or used for alarm output.
Any setting for the web browser control, alarm output, or schedule output is invalid.