66
DL30-G USERS MANUAL EM-8571-G Rev.2
Basic setting (DI)
(1) Once the assignment is complete, configure the following basic setting.
DI setting
2. Enter
1. Enter
Parameter
Description
CH name
Set a channel name using up to 16 characters.
CH comment
Set a description for the channel using up to 16 characters with the tag name, etc.
Invert logic
If the ON/OFF in the input signal and the ON/OFF in the application signal are the reverse of each
other, put a check in the check box.
(2) Specify detailed setting for each of ON and OFF state.
Parameter
Description
Display comment
Set strings corresponding to ON/OFF, respectively using up to 8 characters.
Color
Set the color which represents ON/OFF status displayed on the Web browser view.
ON delay time/
OFF delay time
Set the number of samples for each of the ON and OFF delay times. (Setting range: 0 to 999)
For example, when set to 10, delay time will be 10 seconds (sampling cycle 1 sec. x 10).
Thus, the unit is recognized as being ON when the input signal has been continuously ON for 10
seconds.
Event log
Set whether or not to record the event summary from the Web browser when there is a change in
the input values. Check the box to record event logs.
Event No.
Set the event numbers for ON and OFF, respectively.
The event number is assigned to each event log. (Setting range: 1 to 64)
Message
Set a message to be displayed for each event using up to 32 characters.
Mail template No.
Set the mail template number to be sent when an event occurs.
Multiple mail templates can be specified. Create the templates in advance.
➔
(3) Click [OK] to temporarily store the setting.
Event No.
Message
Color
Web Browser View