Assigning remote I/O to DO
(1) First, perform the I/O slave setting for the remote I/O device.
➔
(2) Click [Discrete output (DO)] button in the [Input/Output] window to display the [Discrete output (DO)] win-
dow.
(3) Double-click a row of the DO channel to be set to display the [DO setting] window.
Input/Output
Discrete output (DO)
1. Click
DO setting
2. Double-click
(4) Set the [CH setting] as [Modbus/TCP], and enter the [Slave No.], [Modbus/TCP register type], and
[Modbus/TCP register address].
Parameter
Description
Slave No.
Enter the slave No. (0 to 31) set in (1).
Modbus/TCP register type
Fixed at [Coil (0X)].
Modbus/TCP register address
Set the register address in the above register type (1 to 65536).