335
Learning Protection Features
Low Battery Voltage Warning Detail Settings
Code
Description
PRT-90 Low
Battery
The low battery voltage warning for RTC function installed in the inverter
can be enabled or disabled. The low battery voltage warning occurs when
the battery voltage is lower than 2 V.
•
Be careful when replacing the battery. Remaining voltage in the battery may cause electric
shock.
•
Make sure that the battery doesn‘t fall inside of the inverter.
6.3 Under load Fault Trip and Warning
The following table lists the under load fault trip and warning features of the H100 series
inverter.
Group Code Name
LCD Display Parameter Setting
Setting range Unit
PRT
23
Under load
detection
Source
UL Source
0
Output
Current
0
–1
-
24
Under load
detection Band
UL Band
10.0
0.0
–100.0
%
25
Under load
warning
selection
UL Warn
Sel
1
Yes
0
–1
-
26
Under load
warning time
UL Warn
Time
10.0
0
–600.0
sec
27
Under load trip
selection
UL Trip Sel
1
Free-Run
-
-
28
Under load trip
timer
UL Trip
Time
30.0
0
–600.0
sec
Summary of Contents for H100
Page 14: ......
Page 18: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 27: ...Preparing the Installation 13 ...
Page 47: ...33 Installing the Inverter ...
Page 48: ...Installing the Inverter 34 Input and Output Control Terminal Block Wiring Diagram ...
Page 61: ...47 Installing the Inverter ...
Page 71: ...Learning to Perform Basic Operations 57 ...
Page 88: ...Learning to Perform Basic Operations 74 ...
Page 103: ...89 Learning Basic Features Code Description V1 Quantizing ...
Page 129: ...115 Learning Basic Features ...
Page 140: ...Learning Basic Features 126 ...
Page 148: ...Learning Basic Features 134 ...
Page 171: ...157 Learning Advanced Features Deceleration dwell operation ...
Page 183: ...169 Learning Advanced Features ...
Page 184: ...Learning Advanced Features 170 PID Command Block ...
Page 185: ...171 Learning Advanced Features PID Feedback Block ...
Page 186: ...Learning Advanced Features 172 PID Output Block ...
Page 187: ...173 Learning Advanced Features PID Output Mode Block ...
Page 197: ...183 Learning Advanced Features ...
Page 201: ...187 Learning Advanced Features Code Description 100 EPID1 Control block ...
Page 202: ...Learning Advanced Features 188 EPID2 Control block ...
Page 237: ...223 Learning Advanced Features Time Period Schedule AP3 38 Except3 Day 01 01 ...
Page 244: ...Learning Advanced Features 230 ...
Page 259: ...245 Learning Advanced Features Code Description Code Description Volt ...
Page 362: ...Learning Protection Features 348 ...
Page 415: ...401 RS 485 Communication Features Item Standards Parity check None ...
Page 524: ...Table of Functions 510 ...
Page 533: ...Table of Functions 519 ...
Page 547: ...533 Troubleshooting ...
Page 585: ...Technical Specification 571 ...
Page 594: ...580 ...
Page 595: ...581 ...
Page 596: ...582 ...