Learning Protection Features
338
6.3.3 Selecting Low Voltage 2 Fault During Operation
Group Code Name
LCD Display
Setting
Setting
range
Unit
PRT
82
Low voltage trip
decision during
operation
Low Voltage2
0
No
0
–1
1
Yes
If input power is disconnected during inverter operation and internal DC voltage decreases
lower than a certain voltage, the inverter disconnects the output and displays low voltage ‗2
(Low Voltage 2)'.
Even if the voltage increases and goes back to the normal state, unlike a low voltage fault, it
remains in a fault state until the user unlocks the fault state.
6.3.4 Output Block via the Multi-function Terminal
When the multi-function input terminal is set as the output block signal terminal and the
signal is input to the terminal, then the operation stops.
Group Code
Name
LCD Display
Parameter
Setting
Setting
range
Unit
IN
65
–
71
Px terminal
setting options
Px Define(Px: P1
–
P7)
5
BX
0-55
-
Output Block by Multi-function Terminal Setting Details
Code
Description
IN-65
–71 Px
Define
When the operation of the multi-
function input terminal is set to ‗5 (BX)‘ and
is turned on during operation, the inverter blocks the output and ‗BX‘ is
displayed on the keypad display. While ‗BX‘ is displayed on the keypad
screen, the inverter‘s operation information including the operation
frequency and current at the time of the BX signal can be monitored. The
inverter resumes operation when the BX terminal turns off and operation
command is input.
Summary of Contents for H100
Page 14: ......
Page 18: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 27: ...Preparing the Installation 13 ...
Page 47: ...33 Installing the Inverter ...
Page 48: ...Installing the Inverter 34 Input and Output Control Terminal Block Wiring Diagram ...
Page 61: ...47 Installing the Inverter ...
Page 71: ...Learning to Perform Basic Operations 57 ...
Page 88: ...Learning to Perform Basic Operations 74 ...
Page 103: ...89 Learning Basic Features Code Description V1 Quantizing ...
Page 129: ...115 Learning Basic Features ...
Page 140: ...Learning Basic Features 126 ...
Page 148: ...Learning Basic Features 134 ...
Page 171: ...157 Learning Advanced Features Deceleration dwell operation ...
Page 183: ...169 Learning Advanced Features ...
Page 184: ...Learning Advanced Features 170 PID Command Block ...
Page 185: ...171 Learning Advanced Features PID Feedback Block ...
Page 186: ...Learning Advanced Features 172 PID Output Block ...
Page 187: ...173 Learning Advanced Features PID Output Mode Block ...
Page 197: ...183 Learning Advanced Features ...
Page 201: ...187 Learning Advanced Features Code Description 100 EPID1 Control block ...
Page 202: ...Learning Advanced Features 188 EPID2 Control block ...
Page 237: ...223 Learning Advanced Features Time Period Schedule AP3 38 Except3 Day 01 01 ...
Page 244: ...Learning Advanced Features 230 ...
Page 259: ...245 Learning Advanced Features Code Description Code Description Volt ...
Page 362: ...Learning Protection Features 348 ...
Page 415: ...401 RS 485 Communication Features Item Standards Parity check None ...
Page 524: ...Table of Functions 510 ...
Page 533: ...Table of Functions 519 ...
Page 547: ...533 Troubleshooting ...
Page 585: ...Technical Specification 571 ...
Page 594: ...580 ...
Page 595: ...581 ...
Page 596: ...582 ...