Learning Advanced Features
200
-
if ADV-10 (PowerOn
Resume) is set to ‗Yes‘, and the terminal input is turned off
instantly after it is turned on (the operation is triggered), and if the inverter is turned
off during a pump clean then is turned back on again, the pump clean operation is
not resumed (because the input terminal is not on when the inverter is turned on).
-
if the terminal input is kept on after it is initially turned on, 1 pump clean cycle is
operated.
5.15 Start & End Ramp Operation
This function is used to rapidly accelerate the pump to the normal operating level, or to
rapidly decelerate the pump and stop it. Start & End ramp operation is performed when
ADV-
24 (Freq Limit) is set to ‗1 (Yes).‘
Group Code Name
LCD Display
Parameter
Setting
Setting Range
Unit
AP2
40
Start & End Ramp
Gradient
Start&End
Ramp
0: No
0 No
-
1 Yes
41
StartRampAcc
StartRampAcc
10.0
0
–600.0
Sec
42
EndRampDec
EndRampDec
10.0
0
–600.0
Sec
ADV
24
Frequency limit
options
Freq Limit
0: No
0 No
-
1 Yes
25
Low Freq minimum
value
Freq Limit Lo
30.00
Start Freq
–
Max Freq
Hz
26
Low Freq
maximum value
Freq Limit Hi
60.00
Freq Limit Lo
–
Max Freq
Hz
Start & End Ramp Operation Setting Details
Code
Description
AP2-40 Start&End
Ramp
Sets the pump Start & End Ramp options.
Setting
Function
0
No
The Start & End Ramp operation is not used.
1
Yes
Use the Start & End Ramp operation.
AP2-41 Start
Ramp Acc
Refers to the time it takes to reach the minimum pump operation
frequency for a Start & End Ramp operation (Freq Limit Lo) set at ADV-25
Summary of Contents for H100
Page 14: ......
Page 18: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 27: ...Preparing the Installation 13 ...
Page 47: ...33 Installing the Inverter ...
Page 48: ...Installing the Inverter 34 Input and Output Control Terminal Block Wiring Diagram ...
Page 61: ...47 Installing the Inverter ...
Page 71: ...Learning to Perform Basic Operations 57 ...
Page 88: ...Learning to Perform Basic Operations 74 ...
Page 103: ...89 Learning Basic Features Code Description V1 Quantizing ...
Page 129: ...115 Learning Basic Features ...
Page 140: ...Learning Basic Features 126 ...
Page 148: ...Learning Basic Features 134 ...
Page 171: ...157 Learning Advanced Features Deceleration dwell operation ...
Page 183: ...169 Learning Advanced Features ...
Page 184: ...Learning Advanced Features 170 PID Command Block ...
Page 185: ...171 Learning Advanced Features PID Feedback Block ...
Page 186: ...Learning Advanced Features 172 PID Output Block ...
Page 187: ...173 Learning Advanced Features PID Output Mode Block ...
Page 197: ...183 Learning Advanced Features ...
Page 201: ...187 Learning Advanced Features Code Description 100 EPID1 Control block ...
Page 202: ...Learning Advanced Features 188 EPID2 Control block ...
Page 237: ...223 Learning Advanced Features Time Period Schedule AP3 38 Except3 Day 01 01 ...
Page 244: ...Learning Advanced Features 230 ...
Page 259: ...245 Learning Advanced Features Code Description Code Description Volt ...
Page 362: ...Learning Protection Features 348 ...
Page 415: ...401 RS 485 Communication Features Item Standards Parity check None ...
Page 524: ...Table of Functions 510 ...
Page 533: ...Table of Functions 519 ...
Page 547: ...533 Troubleshooting ...
Page 585: ...Technical Specification 571 ...
Page 594: ...580 ...
Page 595: ...581 ...
Page 596: ...582 ...