197
Learning Advanced Features
Group Code Name
LCD Display
Parameter
Setting
Setting Range
Unit
31
Operation after
pump clean
PC End
Mode
0
0
Stop
-
1
Run
32
Pump clean
continuous time
limit
PC Limit
Time
10
6
–60
min
33
Pump clean
continuous
number limit
PC Limit
Num
3
0
–10
-
<Basic Pump Clean Operation>
When a pump clean start command is given, the inverter waits until the delay time set at
AP2-19 elapses, accelerates by the acceleration time set at AP2-22, and operates at the
frequency set at AP2-25. The pump runs for the time set at AP2-24, decelerates by the time
set at AP2-23, and then stops. This operation repeats in the forward and reverse directions
(one after another) for the number of times set at AP2-28 (PC Num of Step). Each time the
steps (Fx/Rx) switch, the inverter waits at a stop state for the time set at AP2-21 before
going on with the next step. One step in the forward direction and another step in the
reverse direction makes one cycle. The number of pump clean cycles is set at AP2-30. In
the figure above, AP2-
28 is set to ‗1‘, and AP2-30 is set to ‗1‘.
Pump Clean Function Setting Details
Code
Description
AP2-15 PumpClean
Mode
Sets the pump mode.
Setting
Function
0
None
Pump Clean function is not used.
1
DI
defendant
Set one of the terminal inputs to ‗46 (Pump
Clean Sel)‘ and performs the pump clean
Summary of Contents for H100
Page 14: ......
Page 18: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 27: ...Preparing the Installation 13 ...
Page 47: ...33 Installing the Inverter ...
Page 48: ...Installing the Inverter 34 Input and Output Control Terminal Block Wiring Diagram ...
Page 61: ...47 Installing the Inverter ...
Page 71: ...Learning to Perform Basic Operations 57 ...
Page 88: ...Learning to Perform Basic Operations 74 ...
Page 103: ...89 Learning Basic Features Code Description V1 Quantizing ...
Page 129: ...115 Learning Basic Features ...
Page 140: ...Learning Basic Features 126 ...
Page 148: ...Learning Basic Features 134 ...
Page 171: ...157 Learning Advanced Features Deceleration dwell operation ...
Page 183: ...169 Learning Advanced Features ...
Page 184: ...Learning Advanced Features 170 PID Command Block ...
Page 185: ...171 Learning Advanced Features PID Feedback Block ...
Page 186: ...Learning Advanced Features 172 PID Output Block ...
Page 187: ...173 Learning Advanced Features PID Output Mode Block ...
Page 197: ...183 Learning Advanced Features ...
Page 201: ...187 Learning Advanced Features Code Description 100 EPID1 Control block ...
Page 202: ...Learning Advanced Features 188 EPID2 Control block ...
Page 237: ...223 Learning Advanced Features Time Period Schedule AP3 38 Except3 Day 01 01 ...
Page 244: ...Learning Advanced Features 230 ...
Page 259: ...245 Learning Advanced Features Code Description Code Description Volt ...
Page 362: ...Learning Protection Features 348 ...
Page 415: ...401 RS 485 Communication Features Item Standards Parity check None ...
Page 524: ...Table of Functions 510 ...
Page 533: ...Table of Functions 519 ...
Page 547: ...533 Troubleshooting ...
Page 585: ...Technical Specification 571 ...
Page 594: ...580 ...
Page 595: ...581 ...
Page 596: ...582 ...