Learning Advanced Features
214
Code
Description
DRV-14 Motor
Capacity
Sets the motor capacity to be used. The maximum motor capacity is limited
by the inverter capacity and the keypad only displays the inverter capacity.
BAS-20 Auto
Tuning
Select an auto tuning type and run it. Select one of the options and then
press the [ENT] key to run the auto tuning.
Setting
Function
0
None
Auto tuning function is disabled. Also, if you select
one of the auto tuning options and run it, the
parameter value will revert back to ‗0‘ when the
auto tuning is complete.
1
All (rotating
type)
Measures all motor parameters while the motor is
rotating, including stator resistance (Rs), no-load
current (Noload Curr), rotor time constant (Tr), etc.
Since the motor is rotating while the parameters
are being measured, if the load is connected to the
motor spindle, the parameters may not be
measured accurately. For accurate measurements,
remove the load attached to the motor spindle.
Note that the rotor time constant (Tr) must be
measured in a stopped position.
2
All (static
type)
Measures all parameters while the motor is in the
stopped position, including stator resistance (Rs),
no-load current (Noload Curr), rotor time constant
(Tr), etc. Since the motor is not rotating while the
parameters are measured, the measurements are
not affected when the load is connected to the
motor spindle. However, when measuring
parameters, do not rotate the motor spindle on the
load side.
BAS-14 Noload
Curr,
BAS-21 Rs
–
BAS-24 Tr
Displays motor parameters measured by auto tuning. For parameters that
are not included in the auto tuning measurement list, the default setting will
be displayed.
•
Perform auto tuning ONLY after the motor has completely stopped running.
•
Auto tuning operates when the inverter‘s auto mode is off.
•
Before you run auto tuning, check the motor pole number, rated slip, rated current, rated
voltage, and efficiency on the motor‘s rating plate and enter the data. The default parameter
setting is used for values that are not entered.
•
When measuring all parameters after selecting 2 ( All-static type) at BAS-20: compared with
Summary of Contents for H100
Page 14: ......
Page 18: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 27: ...Preparing the Installation 13 ...
Page 47: ...33 Installing the Inverter ...
Page 48: ...Installing the Inverter 34 Input and Output Control Terminal Block Wiring Diagram ...
Page 61: ...47 Installing the Inverter ...
Page 71: ...Learning to Perform Basic Operations 57 ...
Page 88: ...Learning to Perform Basic Operations 74 ...
Page 103: ...89 Learning Basic Features Code Description V1 Quantizing ...
Page 129: ...115 Learning Basic Features ...
Page 140: ...Learning Basic Features 126 ...
Page 148: ...Learning Basic Features 134 ...
Page 171: ...157 Learning Advanced Features Deceleration dwell operation ...
Page 183: ...169 Learning Advanced Features ...
Page 184: ...Learning Advanced Features 170 PID Command Block ...
Page 185: ...171 Learning Advanced Features PID Feedback Block ...
Page 186: ...Learning Advanced Features 172 PID Output Block ...
Page 187: ...173 Learning Advanced Features PID Output Mode Block ...
Page 197: ...183 Learning Advanced Features ...
Page 201: ...187 Learning Advanced Features Code Description 100 EPID1 Control block ...
Page 202: ...Learning Advanced Features 188 EPID2 Control block ...
Page 237: ...223 Learning Advanced Features Time Period Schedule AP3 38 Except3 Day 01 01 ...
Page 244: ...Learning Advanced Features 230 ...
Page 259: ...245 Learning Advanced Features Code Description Code Description Volt ...
Page 362: ...Learning Protection Features 348 ...
Page 415: ...401 RS 485 Communication Features Item Standards Parity check None ...
Page 524: ...Table of Functions 510 ...
Page 533: ...Table of Functions 519 ...
Page 547: ...533 Troubleshooting ...
Page 585: ...Technical Specification 571 ...
Page 594: ...580 ...
Page 595: ...581 ...
Page 596: ...582 ...