Chapter 5. Function code Table
5-8
Setting data
Functio
n code
Code name
LCD display
Range
Unit
Default
Adjustment
during run
Page
PAR_17 Motor base speed
Base Speed
10.0 ~ 3600.0
rpm
No
6-36
PAR_18 Motor rated voltage
Rated Volt
120 ~ 560
V
No
6-36
PAR_19 Motor number of poles
Pole number
2 ~ 40
Yes
6-36
PAR_20 Motor efficiency
Efficiency
70.0 ~ 100.0
%
Yes
6-36
PAR_21 Motor rated slip
ASR PI Ratio
3 ~ 250
rpm
Yes
6-34~36
PAR_22 Motor rated current
Rated-Curr
1.0 ~ 450.0
A
Yes
6-36
PAR_23
Auto
tuning
type
selection
AutoTuneType
Standstill
Standstill
No
PAR_24 Auto Tuning type select
Auto Tuning
Rs Tuning
None
No
PAR_28 Motor d axis inductance
Ld
0.00 ~ 500.00
mH
Yes
PAR_30 Motor stator resistance
Rs
0.000 ~ 5.000
ohm
Yes
PAR_35
Stimulus detect repeat
count
DetAve Num
1~30
1
No
6-37
PAR_36 Stimulus detect voltage
MagDet Volt
50 ~ 200
V
80
No
6-37
PAR_37 Stimulus detect current
MagDet Curr
10 ~ 150
%
70
No
6-37
PAR_38 Speed drift detect level
RevSpdLevel
0 ~ 100
%
30
No
6-37
PAR_39 Speed drift detect time
RevSpdTime
0 ~ 9999
ms
1500
No
6-37
PAR_40 Trip select bit
MRL TripSel
0000 ~ 1111
BIT
1110
No
6-38
PAR_41
Run command count
for
estimating
Filx
repeatedly
ReDet Num
0 ~ 65535
100
No
6-38
Notice1)
When selecting capacity of the motor(PAR_07), values, PAR_17, 18, 19, 20, 22, 28, 30 will
automatically change. Therefore, please check whether correct values are set or not, comparing with
ones on the plate.
Default of PAR_17, 18, 19, 20, 22, 28, 30 is the standard when PAR_07 is .7kW-NW. Therefore, there is
no indication on user manual.
Notice2)
When PAR_07 is set to “User Define”, PAR_08 will be displayed.