Chapter 4 Loader and Basic Operation
4-12
Connect OC1(multi-function output OC1) of SIO board and P7(multi-
function output OC1) of CN4 with Jumper.
Also, connect each EG of CN3
and CN4 of EG with Jumper. -> When Run, Analog Hold operation
< SIO board terminal wiring diagram schematic>
30C
OC1
2B
EG
30B
RST CM
BRC
P6
BAT
P5
FHM
P4
MM1
P2
MM0
P1
ATO
P3
2A
CM
1A
CM
FX RX
MCC
P7
1B
30A
BX
CN4
CN3
4.8.2 Full Load up operation preparations
1) Load Full persons(100% Load) placing the Elevator into lowest floor.
2)
Run Up operation, setting manual operation speed command as ‘0’
Keypad display
Descriptions
Cursor blinks if pressing [PROG] on DIS_01.
Keep pressing until AI1 Value comes up. Please note the value
displayed.
<in case of Multi-step operation mode>
Please note torque value displayed on initial screen of keypad, setting
manual operation speed command as ‘0’.
<in case of ELIO operation mode>
Please note torque value displayed on initial screen of keypad, setting
manual operation speed command as ‘0’.
In order to show torque value on keypad, please set value on
E/L_58(Display Sel).
4.8.3 No-load operation preparations
1) Make the elevator under No load(No persons) placing the elevator highest floor.
2)
Run Down operation, setting manual operation speed command as ‘0’
Keypad display
Descriptions
Cursor blinks if pressing [PROG] on DIS_01.
Keep pressing until AI1 Value comes up. Please note the value
<in case of Multi-step operation mode>
Please note torque value displayed on initial screen of keypad, setting
manual operation speed command as ‘0’.
DIS
▶
AI1 Value
0
1
100%
▶
0.0rpm SPD
Tq 100% 50A
DIS
▶
AI1 Value
0
1
0%
0.0rpm SPD
Tq -100% -50A
Tq 100% MAN
UP --F 50A
▶