6.3 Parameter group (PAR_[][])
6.3.1 Jump code (PAR_00)
In PAR_00, jumping directly to any parameter code can be accomplished.
(Example) Moving to PAR_30
Press [PROG] and set to 30 using [SHIFT/ESC] / [
▲
(Up)] / [
▼
(Down)] and press [ENT] key. If the desired code
cannot be set (void), the nearest code will be displayed.
PAR
▶
Rs
30 0.346 ohm
Use [
▲
(Up)] / [
▼
(Down)] to move to other codes.
6.3.2 Parameter group function
1) PAR_01 (Parameter initialize)
This is used to initialize all parameters or each group back to the factory defaults. After performing this, be sure to
check PAR_07 (Motor Select) is properly set.
Code
LCD display
Description
Setting range
Unit
Factory
setting
PAR_01 Para.
init
Initialize parameters as factory
defaults
No
All Groups
DIS
I/O
PAR
FUN
CON
EXT
USR
E/L
1)
2ND
No
1) E/L is only displayed when CON_02 ”Application” is set to “Elevator”.
2) PAR_02 ~ 03 (All Parameter Read/Write)
Parameters setting can be copied to other inverters using keypad. To do this, set PAR_02 ‘Parameter Read’ to “Yes”
to upload the parameter setting from the inverter. Take the keypad out and install it to the copied inverter and set
PAR_03 ‘Parameter Write’ to “Yes” to download the function parameters.
Code
LCD display
Description
Setting range
Unit
Factory
setting
PAR_02
Para. Read
All Paramter Read
No
Yes
No
PAR_03
Para. Write
All Paramter Write
No
Yes
No