Chapter 6. Function Description (I/O)
※
Cross reference table for
1
st
function and& 2
nd
function
Parameter
2
nd
function
1
st
function
Acceleration time
2nd_09
2nd Acc time
FUN_40
Acc. Time 1
Deceleration time
2nd_10
2nd Dec time
FUN_41
Dec. time 1
Encoder-related
parameter
2nd_12 ~ 2nd_14
PAR_11 ~ PAR_15
Motor constants
2nd_15 ~ 2nd_26
PAR_16 ~ PAR 30
Electronic thermal level
for 1 min
2nd_32
2nd ETH 1min
FUN_55
ETH 1min
Electronic thermal level
for continous
2nd_33
2nd ETH Cont
FUN_56
ETH Cont
※
Note : 1
st
& 2
nd
function switch-over should be selected when the motor is stopped.
If selected during RUN, 2
nd
function is not active until motor stop.
1.12) XCEL-L
1.13) XCEL-H
Refer to FUN_40 ~ 47 (Accel/ Decel time 1, 2, 3, 4).
Code
LCD display
Description
Factory setting
FUN_40
Acc Time-1
Accel time 1
2.00(sec)
FUN_41
Dec Time-1
Decel time 1
2.00(sec)
FUN_42
Acc Time-2
Accel time 2
3.00(sec)
FUN_43
Dec Time-2
Decel time 2
3.00(sec)
FUN_44
Acc Time-3
Accel time 3
4.00(sec)
FUN_45
Dec Time-3
Decel time 3
4.00(sec)
FUN_46
Acc Time-4
Accel time 4
5.00(sec)
FUN_47
Dec Time-4
Decel time 4
5.00(sec)