56
WWW.LCMETER.COM
LCI40
Series IOM
6 oPeration
No.
Function
Settings / Descriptions
C3._ Frequency Output X
C3.3.11
Special Functions
This function is only available at the terminal B frequency output. At the same time, 2
frequency outputs must be available:
1st output at terminal A or D / 2nd output at terminal B
The B output is operated as a slave output, controlled and set using master output A or D
Select:
Off (no phase shift) /
Phase Shift w.r.t. D or A (slave output is B and master output is D or A)
C3._.12
Information
Serial no. of the I/O board, software version no. and production date of the circuit board
C3._.13
Simulation
Sequence see B1._ Frequency Output X
C3._ Pulse Output X
C3._
Pulse Output X
X stands for one of the connection terminals A, B or D_ stands for Fct. C3.2 (A) / C3.3 (B) /
C3.5 (D)
C3._.1
Pulse Shape
Specify the pulse shape
Select:
Symmetric (about 50% on and 50% off) /
Automatic (constant pulse with about 50% on and 50% off at 100% pulse
rate) /
Fixed (fixed pulse rate, setting see below Fct. C3._.3 100% pulse rate)
C3._.2
Pulse Width
Only available if set to “Fixed” in Fct. C3._.1.
Range: 0.05 - 2000 ms
Note: max. setting value Tp [ms]
≤
500 / max. pulse rate [1/s], gives the pulse width = time
where the output is activated
C3._.3
Max. Pulse Rate
Pulse rate for 100% of the measuring range
Range: 0.0 - 10000 1/s
Limitation 100% pulse rate
≤
100/s: Imax
≤
100 mA
Limitation 100% pulse rate > 100/s: Imax
≤
20 mA
C3._.4
Measurement
Measurements for activating the output
Select: Volume Flow / Mass Flow
C3._.5
Pulse Value Unit
Selection of the unit from a list, depending on the “measurement”
C3._.6
Value Per Pulse
Set value for volume or mass per pulse
xxx.xxx, measured value in [l] or [kg] depending on setting in C3._.6
At max. pulse rate see above 3._.3 “Pulse Output”
6.4 Function tables
6.4.3 Menu C, Setup, continued